Section 5 - Warnings/Faults
112
NOTES
Note 3:
Subtypes Decimal Description
Fault 2 Event
Bits
1
CRCerrorinsafetycriticalRAMblock
2
ErrorreloadingsafetycriticalRAMblockfromEEPROM
4
ErrorloadingdatafromPersonalityboard
8
Excelsignallevelhasbeenbelowthelowsignallevel
thresholdforatleast24hours
16
Excelbeamblocked
32
Personalityboarderrorcode>0
64
Optionboarderrorcode>0
128
IRmAinput>1mAand<3�4mA
256
IRmAinput<1�0mA
512
IRforced10mAnotwithin+/-1mA
1024
gainsfromPGAdon'tmatchlocalcopy
2048
errorreadingorwritingEEPROM
4096
ECCreexfailure
8192
RAMtestfailure
16384
ProgrammemoryCRCfailure
32768
Opcodetestfailure
Fault 3 Event
Bits
1 Interruptintegritytestfailure
Note 4:
OptimaandExcelfaultandwarningcodesaredisplayedintheEventHistorydataeld�