EasyManuals Logo

Honeywell XNX Technical Manual

Honeywell XNX
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #138 background imageLoading...
Page #138 background image
XNX Universal Transmitter
Section 6 - Specications
136
Gas type Part Number Gas Type Applied Concentration Unit Reading Unit
H
2
S
XNXXSH1SS
XNXXSH1FM
Ammonia 50
ppm
0 ppmH
2
S
CarbonMonoxide 100 <2 ppmH
2
S
CarbonDioxide 5000 0 ppmH
2
S
Chlorine 0.5 0 ppmH
2
S
Ethylene 100 0 ppmH
2
S
Hydrogen 100 0 ppmH
2
S
HydrogenSulfide 10 10 ppmH
2
S
NitrogenMonoxide 25 0 ppmH
2
S
NitrogenDioxide 3 0 ppmH
2
S
SulfurDioxide 2 0 ppmH
2
S
H
2
S
(HighRange)
XNXXSH2SS
Ammonia 50
ppm
0 ppmH
2
S
CarbonMonoxide 100 <2 ppmH
2
S
CarbonDioxide 5000 0 ppmH
2
S
Chlorine 0.5 0 ppmH
2
S
Ethylene 100 0 ppmH
2
S
Hydrogen 100 0 ppmH
2
S
HydrogenSulfide 10 10 ppmH
2
S
NitrogenMonoxide 25 0 ppmH
2
S
NitrogenDioxide 3 0 ppmH
2
S
SulfurDioxide 2 0 ppmH
2
S

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
Ingress ProtectionIP66/67
Product TypeUniversal Transmitter
Enclosure RatingIP66/67
DisplayLCD
Communication ProtocolsHART, Modbus, Foundation Fieldbus
Power Supply24 VDC nominal, 18-32 VDC
Operating Temperature-40°C to +65°C (-40°F to +149°F)
MaterialAluminum or Stainless Steel
Gas TypesToxic, Oxygen, and Combustible gases
Output4-20 mA
Relays3 programmable relays
ApprovalsATEX, IECEx, UL, CSA
Sensor CompatibilityElectrochemical, catalytic, infrared, and other sensor types