Install a PE (protective earthing) conductor that is identical in size, insulation
material, and thickness to the branch-circuit supply conductors. The PE conductor
insulation must be green with yellow stripes. The earthing conductor is to be
connected from the unit to the building installation earth or, if supplied by a
separately derived system, at the supply transformer or motor-generator set
grounding point.
WARNING NORDIC Class 1 Equipment
Denmark: Før tilslutning af de øvrige ledere, se medfølgende
installationsvejledning.
WARNING NORDIC Class 1 Equipment
Sweden: Apparaten skall anslutas till jordat uttag, när den ansluts till ett nätverk.
Disconnect DevicesDisconnect devices or circuit breakers must be used to protect the system against
abnormal hazards. Table 3 details the circuit breaker specifications.
WARNING Provide a disconnect device to protect against abnormal hazards.
Systems configured with a full complement of cells, memory, and I/O and connected
to a 5-wire source must have a maximum 60A 3-phase with neutral (4-pole) circuit
breaker installed as part of the building installation.
Systems configured with a full complement of cells, memory, and I/O and connected
to a 4-wire source must have a maximum 80A 3-phase (3-pole) circuit breaker
installed as part of the building installation.
Table 3 Wall Disconnect Device Circuit Breaker Specification
Agency approvals: UL, CSA, VDE
Interrupt capacity 5,000A minimum
Breaker type Magnetic trip
Voltage rating Delta 250V minimum, WYE 420V minimum
Input Source Delta 3 pole + PE, WYE 4 pole + PE
Circuit Interruption Simultaneous trip of all poles
Ground The PE (Protective Earth Ground) wire is not
switched