Shenzhen Hpmont Technology Co., Ltd Appendix A Parameters
HD30 Series Inverters User Manual -145-
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
F00.16 Interval of jog operation 0.0-100.0s 0.0s 0.1s ×
F00.17
Operation direction
selection
0: The same as run
command
1: Opposite to run command
0 1 ×
F00.18 Anti-reverse operation
0: Reverse operation is
permitted
1: Reverse operation is
prohibitted
0 1 ×
F00.19
Dead time of direction
switch
0.0-3600.0s 0.0s 0.1s ×
F00.20
Key enable of optional
display panel
0: Enabled
1: Disabled
0 1 ○
F00.21
Dormant function
selection
0: Disabled
1: Enabled
0 1 ×
F00.22
Dormancy wake up
time
0.0-360.0s 0.0s 0.1s ○
Group F01 Protection of Parameters ( refer to pages 62
64)
F01.00 User’s password 00000-65535 0 1 ○
F01.01 Menu mode selection
Units:
0: Full menu mode
1: Checking menu mode
(Only different from factory
setting parameters can be
displayed)
Tens:
0: Does not lock the
parameter mapping
relationship of Group U and
Group F
1: Lock the parameter
mapping relationship of
Group U and Group F
10 1 ○
F01.02
Function code
parameter initialization
0: No operation
1: Restore to factory settings
2: Download the display
panel EEPROM parameter 1
to the current function code
settings
3: Download the display
panel EEPROM parameter 2
to the current function code
settings
4: Clear fault information
5: Download the display
panel EEPROM parameter 1
to the current function code
0 1 ×
A