Appendix A Parameters Shenzhen Hpmont Technology Co., Ltd
―146― HD30 Series Inverters User Manual
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
settings (including the motor
parameters).
6: Download the display
panel EEPROM parameter 2
to the current function code
settings (including the motor
parameters).
F01.03
Display panel
EEPROM parameter
initialization
0: No operation
1: Upload the current
function code settings to the
display panel EEPROM
parameter 1
2: Upload the current
function code settings to the
display panel EEPROM
parameter 2
0 1 ○
Group F02 Run/Stop Control Parameters (refer to pages 64
68)
F02.00 Start mode selection
0: From the DWELL
frequency to start
1: Brake first and then start
from DWELL frequency
2: Start after speed tracking.
If the result of speed tracking
is smaller than F02.02, it will
start from the starting
DWELL frequency
0 1 ×
F02.01 Starting delay time 0.00-10.00s 0.00s 0.01s ×
F02.02
Start DWELL
frequency setting
0.00-upper limit 0.00Hz 0.01Hz ×
F02.03
Retention time of
starting DWELL
frequency
0.00-10.00s 0.00s 0.01s ×
F02.04
DC braking current
setting
0-100% (inverter’s rated
current)
50% 1% ×
F02.05
DC braking time at
start
0.00-60.00s 0.50s 0.01s ×
F02.06
Speed tracking mode
selection
0: Searching based on
residual voltage
1: Searching based on
current
0 1 ×
F02.07
Speed search mode
based on current
0: From the max. output
frequency to start speed
searching
1: From the stopping
frequency to start speed
searching
1 1 ×
F02.08
Setting reference 0-100% (motor’s rated
50% 1% ×