Shenzhen Hpmont Technology Co., Ltd Appendix A Parameters
HD30 Series Inverters User Manual 157
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
Group F11 Reserved
Group F12 Reserved
Group F13 Asynchronous Motor 2 Parameters (refer to pages 86
88)
F13.00
Control mode selection
of motor 2
0: V/f control without PG
1: Reserved
2: Vector control without PG
0 1 ×
F13.01 Rated power of motor 2 0.2500.0kW
Dependent
on inverter
model
0.1kW ×
F13.02
Rated voltage of motor
2
0inverter rated voltage 1V ×
F13.03
Rated current of motor
2
5.5kW above: 0.0999.9A 0.1A
×
5.5kW or below: 0.00
99.99A
0.01A
F13.04
Rated frequency of
motor 2
1.0400.0Hz 50.0Hz 0.1Hz ×
F13.05 Rated speed of motor 2 124000rpm 1500rpm 1rpm ×
F13.06 Power factor of motor 2 0.0011.000
Dependent
on inverter
model
0.001 ×
F13.07
Parameter auto-tuning
of motor 2
0: Auto-tuning is disabled
1: Stationary auto-tuning
2: Rotary auto-tuning
0 1 ×
F13.08
Stator resistance of
motor 2
5.5kW above: 0.000
9.999Ω
Dependent
on inverter
model
0.001Ω
×
5.5kW or below: 0.00
99.99Ω
0.01Ω
F13.09
Rotor resistance of
motor 2
5.5kW above: 0.000
9.999Ω
0.001Ω
×
5.5kW or below: 0.00
99.99Ω
0.01Ω
F13.10
Leakage inductance of
motor 2
5.5kW or below: 0.00
500.00mH
0.01m
H
×
5.5kW or below: 0.0
5000.0mH
0.1mH
F13.11
Mutual inductance of
motor 2
5.5kW above: 0.00
500.00mH
0.01m
H
×
5.5kW or below: 0.0
5000.0mH
0.1mH
F13.12
Idling exciting current
of motor 2
5.5kW above: 0.0999.9A 0.1A
×
5.5kW or below: 0.00
99.99A
0.01A
F13.13 Reserved
F13.14 Reserved
F13.15 Reserved
F13.16
V/f curve selection of
0: Line 0 1 ×
A