Appendix A Parameters Shenzhen Hpmont Technology Co., Ltd
158 HD30 Series Inverters User Manual
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
motor 2 1: Square curve
2: 1.2 exponential curve
3: 1.7 exponential curve
4: User-defined curve
F13.17
V/f frequency value F3
of motor 2
F13.19F13.04 0.00Hz 0.01Hz ×
F13.18
V/f voltage value V3 of
motor 2
F13.20F13.02 0V 1V ×
F13.19
V/f frequency value F2
of motor 2
F13.21F13.17 0.00Hz 0.01Hz ×
F13.20
V/f voltage value V2 of
motor 2
F13.22F13.18 0V 1V ×
F13.21
V/f frequency value F1
of motor 2
0.00F13.19 0.00Hz 0.01Hz ×
F13.22
V/f voltage value V1 of
motor 2
0F13.20 0V 1V ×
F13.23
Torque boost of motor
2
0.030.0%
0.0: Auto torque boost
45kW and
below: 2.0%
55132 kW
inverter:
1.0%
160kW and
above:
0.5%
0.1% ×
F13.24
Cut-off point used for
manual torque boost of
motor 2
0.050.0% (F13.04) 30.0% 0.1%
F13.25
Slip compensation gain
of motor 2
0.0300.0% 100.0% 0.1%
F13.26
Slip compensation filter
time of motor 2
0.0110.00s 0.10s 0.01s
F13.27
Slip compensation
limitation of motor 2
0.0%250.0% 200.0% 0.1% ×
F13.28
Compensation
constant of motor 2
0.125.0s 2.0s 0.1s
F13.29 Reserved
F13.30
AVR function of motor
2
0: Disabled
1: Enabled all the time
2: Disabled in deceleration
process
1 1
F13.31
Oscillation-suppression
mode of motor 2
0: Oscillation suppression is
dependent on the motor’s
exciting current component
1: Oscillation suppression is
1 1