Shenzhen Hpmont Technology Co., Ltd Appendix A Parameters
HD30 Series Inverters User Manual -171-
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
when power on
F19.08
Cooling fan controls
delaying time
0.0-600.0s 30.0s 0.1s ○
F19.09 Droop control 0.00-10.00Hz 0.00Hz 0.01Hz ×
F19.10
Zero-frequency
threshold
0.00-upper limit 1.00 Hz 0.01Hz ○
F19.11
Action selection at
setting frequency is
lower than
zero-frequency
threshold
0: Run according to
frequency command
1: Holding stop, no output
2: Run according to
zero-frequency threshold
3: Run according to
zero-frequency
0 1 ×
F19.12
Trip-free selection at
momentary power loss
0: This function is disabled
1: This function is enabled
0 1 ×
F19.13
Deceleration time at
voltage compensation
0.1-6000.0s 5.0s 0.1s ○
F19.14
Voltage rise diagnosis
time of trip-free
operation at
momentary power loss
0.00-10.00s 0.10s 0.01s ○
F19.15
Reference voltage of
trip-free operation at
momentary power loss
0-1200V
220V
inverter:
248V;
380V
inverter:
430V
1V ×
F19.16
Restart after power
failure
0: This function is disabled
1: This function is enabled
0 1 ×
F19.17
Delay time for restart
after power failure
0.00-10.00s 2.00s 0.01s ○
F19.18
Protection of stall
overvoltage
0: Disabled (with braking
resistance)
1: Enabled
1 1 ×
F19.19 Stall overvoltage point 0-1200V
220V
inverter:
390V;
380V
inverter:
740V
1V ×
F19.20
Auto current limiting
selection
0: Disabled
1: Enabled in Acc./Dec.
running process, but
disabled in constant speed
runnng process
2: Enabled both in Acc./Dec.
1 1 ×