8.8 (Optional) Connecting a Remote EPO Cable
NO TICE
The EPO switch can be connected to the device and can be associated with
DIN1/DIN2 through software conguration. By default, the EPO switch is
closed.
Press and hold the EPO switch for 3s to shut down the entire system (including
the DG).
The connection position of the EPO switch must be
dierent from the mains
detection position of the ATS.
Prepare the EPO switch and cable before installation. The recommended cable
size is 22 AWG.
Equip the EPO switch with a protective cover to prevent misoperations, and
protect the cable with a protective tube.