Figure 8-87 Installing battery signal cables
----End
8.8 (Optional) Connecting a Remote EPO Cable
● The EPO switch can be connected to the device and can be associated with
DIN1/DIN2 through software conguration. By default, the EPO switch is
closed.
● Press and hold the EPO switch for 3s to shut down the entire system (including
the DG).
● The connection position of the EPO switch must be
dierent from the mains
detection position of the ATS.
● Prepare the EPO switch and cable before installation. The recommended cable
size is 22 AWG.
● Equip the EPO switch with a protective cover to prevent misoperations, and
protect the cable with a protective tube.
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1) 8 Electrical Connection
Issue 01 (2022-07-15) Copyright © Huawei Technologies Co., Ltd. 156