10 System Maintenance
10.1 System Power-O
10.2 Routine Maintenance
10.3 Troubleshooting
10.4 Battery Storage and Recharge
10.5 Storage with Low SOC
10.1 System Power-O
Precautions
● After the system powers o, the remaining electricity and heat may still cause
electric shocks and body burns. Therefore, wear protective gloves 5 minutes
after the system is powered
o before performing any operation. Maintain
the product after all indicators are o.
● When an iSitePower system is running, turning o the DC SWITCH of the
product cannot completely power o the system. In this case, you cannot
perform maintenance operations on the product.
Powering
O the System
Step 1 Switch o the upstream AC input circuit breaker for the iSitePower-M system.
Step 2 Set the DC SWITCH on the power module to OFF.
Step 3 Hold down the manual ON/OFF switch for 5s to shut down the battery module.
----End
10.2 Routine Maintenance
To ensure that the power system operates properly for a long term, you are
advised to perform routine maintenance as described in this chapter.
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1) 10 System Maintenance
Issue 01 (2022-07-15) Copyright © Huawei Technologies Co., Ltd. 165