7.2.3 Genset-Grid Hybrid Scenario
Table 7-7 Cables in Single-node system (capacity expansion scenario)
No. One End Other End Type Recommended
Specications
1 AC output PDB
customer
side
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm
2 AC input PDC
customer
side
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm
3 COM and
dry contact
ports
Genset
control
signal/ATS
Outdoor shielded twisted
pair cable (8 cores)
Conductor cross-
sectional area: 0.2–1
mm
2
Cable outer diameter:
6.3–7.5 mm
4 Ground
point
Ground bar
customer
side
Outdoor single-core
copper cable
Main ground cable: 4–6
mm
2
(same as the cross-
sectional area of the AC
input power cable)
5 Ground
point
Ground point
on the
module for
capacity
expansion
Outdoor single-core
copper cable
Main ground cable: 6 mm
2
Table 7-8 Cables in parallel system scenario
No.
One End Other End Type Recommended
Specications
1 Ground
point
Ground bar
customer
side
Outdoor single-core
copper cable
Main ground cable: 4–6
mm
2
(same as the cross-
sectional area of the AC
input power cable)
2 COM and
dry contact
ports
Genset
control
signal/ATS
Outdoor shielded twisted
pair cable (8 cores)
Conductor cross-
sectional area: 0.2–1
mm
2
Cable outer diameter:
6.3–7.5 mm
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1) 7 Preparing Cables
Issue 01 (2022-07-15) Copyright © Huawei Technologies Co., Ltd. 66