Figure B-3 Preparing a PV input power cable
B.4 Stripping Length
Figure B-4 Stripping length
Table B-1 Denition of the cable stripping length (standard scenario)
No.
One End Other End 1 2
1 PV input
ports
DC switch
(customer
side)
N/A 8–10 mm
2 AC output PDB
(customer
side)
100 mm PE wire: 7 mm
L/N wire: 17 mm
3 AC output PDB
(customer
side)
75 mm PE wire: 7 mm
L/N wire: 17 mm
4 Ground point Ground bar
(customer
side)
N/A 7 mm