No. One End Other End Type Recommended
Specications
7 AC parallel
box
Ground bar
customer
side
Outdoor single-core
copper cable
Conductor cross-
sectional area: 25 mm
2
Cable outer diameter: 8–
11 mm
7.2.5 Solar-Genset Hybrid Scenario
Table 7-11 Cables in Single-node system (capacity expansion scenario)
No. One End Other End Type Recommended
Specications
1 PV input
ports
DC switch
customer
side
Common outdoor PV
cable in the industry
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
5.5–9 mm
2 AC output PDB
customer
side
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm
3 AC input PDC
customer
side
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm
4 COM and
dry contact
ports
Genset
Control
Signal
Outdoor shielded twisted
pair cable (8 cores)
Conductor cross-
sectional area: 0.2–1
mm
2
Cable outer diameter:
6.3–7.5 mm
5 Ground
point
Ground bar
customer
side
Outdoor single-core
copper cable
Main ground cable: 4–6
mm
2
(same as the cross-
sectional area of the AC
input power cable)
6 Ground
point
Ground point
on the
module for
capacity
expansion
Outdoor single-core
copper cable
Main ground cable: 6 mm
2
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1) 7 Preparing Cables