EasyManua.ls Logo

Huawei iSitePower-M V100R002C00 - Cables Prepared by the Customer

Huawei iSitePower-M V100R002C00
197 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 7-2 (Optional) Cables in capacity expansion scenario
No. Cable Type
1 Battery power cable
bottom cascading
cables
Common outdoor PV cable in the industry
2 Battery signal cable
bottom cascading
cables
Outdoor shielded twisted pair cable
7.2 Cables prepared by the customer
7.2.1 Solar-Only Scenario
Table 7-3 Cables in Single-node system (capacity expansion scenario)
No. One End Other End Type Recommended
Specications
1 PV input
ports
DC switch
customer
side
Common outdoor PV
cable in the industry
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
5.5–9 mm
2 AC output PDB
customer
side
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm
3 Ground
point
Ground bar
customer
side
Outdoor single-core
copper cable
Main ground cable: 4–6
mm
2
(same as the cross-
sectional area of the AC
input power cable)
4 Ground
point
Ground point
on the
module for
capacity
expansion
Outdoor single-core
copper cable
Main ground cable: 6 mm
2
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1) 7 Preparing Cables
Issue 01 (2022-07-15) Copyright © Huawei Technologies Co., Ltd. 63

Table of Contents