7 Preparing Cables
NO TICE
Do not use aluminum cables to avoid electrochemical corrosion of copper and
aluminum.
Power cables should be able to withstand a temperature of at least 90°C.
NO TE
The minimum cable diameter must comply with local cable standards.
The factors that aect cable selection include the rated current, cable type, routing
mode, ambient temperature, and maximum expected line loss.
7.1 Cables delivered with the product
7.2 Cables prepared by the customer
7.1 Cables delivered with the product
Table 7-1 Cables delivered with the product
No.
Cable Type
1 Battery power cable Common outdoor PV cable in the industry
2 Battery signal cable Outdoor shielded twisted pair cable
3 Ground cable
(standard scenario)
Outdoor single-core copper cable
NO TICE
In capacity expansion scenarios, you need to purchase power cables and signal
cables for bottom cascading from Huawei.
iSitePower-M V100R002C00 User Manual