9 System Commissioning
9.1 System Power-On
9.2 Battery Commissioning
9.1 System Power-On
● The product must be powered on within 24 hours after being unpacked. During
maintenance, the
power-o time cannot exceed 24 hours.
● When there is no PV input and batteries are out of power, the product cannot
be started. You need to manually clear the alarm on the app.
Procedure
Step 1 Turn on the corresponding switch based on the scenario.
● If there is PV input, turn on the DC SWITCH.
● If there is no PV input, hold down the manual ON/OFF switch for 5s.
Step 2 Switch on the upstream AC input circuit breaker for the iSitePower-M system.
Step 3 After the initial installation and power-on, observe the LED indicator to check the
running status.
----End