Loading...
No. One End Other End Type Recommended
Specications
3 AC parallel
box
PDB
customer
side
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 25 mm
2
Cable outer diameter:
16–26 mm
4 AC parallel
box
AC output Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm
5 AC parallel
box
AC input Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm
6 AC parallel
box
PDC
customer
side
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 25 mm
2
Cable outer diameter:
16–26 mm
7 AC parallel
box
Ground bar
customer
side
Outdoor single-core
copper cable
Conductor cross-
sectional area: 25 mm
2
Cable outer diameter: 8–
11 mm
7.2.4 Solar-Grid Hybrid Scenario
Table 7-9 Cables in Single-node system (capacity expansion scenario)
No.
One End Other End Type Recommended
Specications
1 PV input
ports
DC switch
customer
side
Common outdoor PV
cable in the industry
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
5.5–9 mm
2 AC output PDB
customer
side
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm
3 AC input PDC
customer
side
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm