Figure 2-8 System congurations
NO TE
Maximum capacity:
1. In a single-node system, a maximum of six battery modules can be connected.
2. In a parallel system, a maximum of three power modules can be connected. Each
power module can connect to a maximum of three battery modules.
In a parallel system, three routes of single-phase output can be combined but they
cannot be used as three-phase output.
In parallel connection scenarios, the number of battery modules on the master and
slave products must be the same.
Table 2-4 Recommended battery conguration
Scenario
Number of
Power Modules
Number of
Battery Modules
System Capacity
Single-node
system
1 1 3kVA/5kW
2 6kVA/10kW
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1) 2 Product Description
Issue 01 (2022-07-15) Copyright © Huawei Technologies Co., Ltd. 23