EasyManua.ls Logo

Hunter X-CORE

Hunter X-CORE
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ADVANCED FEATURES (CONTINUED)
Use the or buttons and the and buttons to navigate through
the Custom, K-Factor, and Offset screen. Once you navigate to a number,
it will ash. The number may be changed by pressing the + / button to
either increase or decrease the value. Once you have completed entering
the K-Factor and Offset specied by the manufacturer of the ow sensor,
use the button to return to the main Sensor Conguration screen.
If an HFS sensor has been selected and programmed in the Sensor
Conguration screen, the main RUN screen will indicate a ashing ow rate
anytime a station is irrigating. If the station's ow has not been learned or the
station has not been enabled for ow monitoring, which will be discussed
in the Flow Operation and Manual Operation section, the screen will still
indicate a total ow of 0.0 GPM because the HFS has been selected.
Flow Operation
The Flow Operation feature allows you to program ow monitoring
functions for each station. You can program the controller to either monitor
ow for a station or not monitor ow for a station.
1.
Turn the dial to the ADVANCED FEATURES position. Use the and
to select Flow Operation and use the + button to enter.
2. Use the and buttons to navigate to the station you would like
to program.
3. The cursor will be displayed next to Monitored. Use the + / button
to enable or disable ow monitoring for that station.
If ow monitoring is enabled (Yes), you will be given the ability to change
certain characteristics of each stations monitored ow. As soon as the
station is enabled the new screen will appear with the following selections:
• Expected Flow – the amount of ow expected for that station in
Gallons Per Minute (GPM )or Liters Per Minute (LPM)
• Overow – Can be set from 110% to 300% of Expected Flow. During
system operation, if the station ow exceeds the Overow limit, the
controller will shut the system down and begin diagnostic testing. For
example, if the expected ow is 20 GPM and the overow is set to
115%, the actual ow would need to exceed 15% (3 gallons) of the
expected ow. Therefore, the station would need to exceed 23 GPM
before the controller would go into overow alarm.
• Underow – Can be set from 10% to 100% of Expected Flow. During
system operation, if the actual station ow falls below the Underow
limit, the controller will shut the system down. For example, if the
expected ow is 20 GPM and the underow is set to 50%, the actual
ow would need to underow by 50% (10 gallons) of the expected
ow. Therefore, the station would need to ow at a minimum of 10
GPM before the controller would go into an underow alarm.
• Start Delay – Can be set from 5 seconds to 10 minutes. The Start
Delay prevents premature system shutdown due to erratic ow within
the mainline by providing a delay before the system shutdown occurs.
It allows the system to stabilize prior to shutting the system down
during Overow and Underow conditions.
After the station has been enabled, press the button to select any of
the features mentioned above. With the cursor pointing to the ow
characteristic, press the + / button to increase or decrease the value until
the desired number is reached.
If ow monitoring is enabled for a specic station, the factory preset
values will be displayed. The expected ow will be blank, because the
actual learning process has not taken place. The learning process will be
discussed in the Manual Operation, Learn Expected Flow section. Overow
will be 115%, underow will be 50%, and the preset Start Delay will be set
to 1 minute.
Flow Operation is necessary to program in order for the controller to know
which stations to monitor. Important additional steps that need to be taken
to complete the ow monitoring setup. A ow sensor needs to be assigned
in the Sensor Conguration screen, and the stations set to be monitored
need their ows to be learned. These steps are required in order for ow
monitoring to occur.
If a station has been enabled for ow monitoring, it is important to know
that the System Status Dashboard ow light will become active for that
station. If the other components to complete the ow monitoring process
have not been programmed, but the station’s ow has been enabled, the
System Status Flow light will light Green indicating a normal ow.
A detailed description of what happens in the case of an overow or
underow is discussed in the controller Diagnostics and Troubleshooting
section under System Status Dashboard, Flow. It is very important to read
and understand this description before ow monitoring occurs.
23

Table of Contents

Other manuals for Hunter X-CORE

Related product manuals