OVERVIEW
The scope of this section is limited to main
field wiring connections and to the control
panel. Hussmann’s Super Plus C o n t r o l
Panels feature custom wiring schematics. Most
of the common user choices are detailed in this
section. For a schematic of the control panel as
shipped, see the diagrams on the panel. T h e r e
are three:
Compressor Control Circuit Diagram
Defrost Diagram
Power and Accessories Diagram.
The Fibertronic Circuit Boards are discussed
at length. Both explanation of Board layout
and a troubleshooting chart to determine
Board continuity are here. The Super Plus
System is available wired for 208-230/3/60 or
460/3/60 or other international voltages. In
any case, the control circuit is 120V. Refer to
the serial plate located on the control panel to
determine wire size (MCA) and overcurrent
protection (MOPD).
FIELD WIRING
Super Plus components are wired as com-
pletely as possible at the factory with all work
completed in accordance with the National
Electrical Code (NEC). All deviations
required by governing electric codes will be
the responsibility of the installer.
The lugs on the circuit breaker package in the
compressor control panel are sized for copper
wire only, with 75
O
C T H W insulation. A l l
wiring must be in compliance with governing
electrical codes.
For Remote Header Defrost Assembly:
To the remote defrost control panel provide
one 120V 1PH 15A branch circuit.
Between the remote defrost control panel and
the Super Plus System provide
one 120V 15A 2-wire circuit.
For 208-230/3/60 Compressor Units:
To each Super Plus System rack provide
one 208-230/3/60 branch circuit
one 120V 1PH 30A circuit—omit w h e n
single point connection kit is used.
To each remote air-cooled condenser provide
one 208-230/3/60 branch circuit.
For 460/3/60 Compressor Units:
To each Super Plus System rack provide
one 460/3/60 branch circuit
one 120V 1PH 30A circuit—omit when
single point connection kit is used.
To each remote air-cooled condenser provide
one 460/3/60 branch circuit.
ForAlarm Wiring
Between the Compressor Control Panel and
the in store alarm bell provide
one 120/1/60 10A circuit.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 • Printed in USA
Revised August 1, 1996 P/N 340272A
4 - 1