EasyManua.ls Logo

ICD NeoGCP i7 PLUS+ - Page 2

ICD NeoGCP i7 PLUS+
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
REV. N
NeoGCP i7 PLUS+
- 2 -
C A U T I O N
1. It is recommended to use RPM measurement method as MPU to prevent start motor damage when using
Doosan engine.
2. If RPM measurement method is frequency, oil pressure switch is set to not use, and voltage is not
generated at engine CRANK-ON, the start motor may be damaged.
MPU Method Setup
Menu
Setup
TEETH(FACTOR)
1. Select [SYSTEM] then [ENTER] on Menu screen.
2. Press [] 2 times, [] 2 times, select [TEETH(FACTOR)], then press [ENTER].
3. Input Teeth number, then press [ENTER].
RUN-STATE OP-
SWITCH
Use / Not use
1. Select [CONTROL] then [ENTER] on Menu screen.
2. Press [] 3 times, [] 2 times, select [OIL PRESS SENSOR] then [ENTER].
3. Select [Use] then press [ENTER].
RUN-STATE OP-
GAUGE
1. Select [CONTROL] then [ENTER] on Menu screen.
2. Press [] 3 times, [] 1 time, select [RUN-STATE OP-GAUGE] then setup oil
pressure.
6.5 Refer to Crank ON/OFF
Doosan Engine Gear Teeth
Gear Teeth
Doosan Engine Model
129
DB33, PO34TI, DB58
140
D1146, D1146T
146
PO86TI
152
P126TI-3, P126TI, P126TI-II
160
P158LE-III, P158LE, P158LE-1, P158LE-2, P180LE-II, P158LE, P222LE-1, P222LE,
P222LE-II, P222FE-II
Information above written in request of Doosan Commercial Engine(DSCE).
Start motor ON/OFF record stored in ALARM HISTORY.
If start motor is damaged due to ignoring above caution, free A/S from DSCE will NOT be possible
even within warranty period.