C A U T I O N
1. It is recommended to use RPM measurement method as MPU to prevent start motor damage when using
Doosan engine.
2. If RPM measurement method is frequency, oil pressure switch is set to not use, and voltage is not
generated at engine CRANK-ON, the start motor may be damaged.
■ MPU Method Setup
1. Select [SYSTEM] then [ENTER] on Menu screen.
2. Press [▼] 2 times, [▶] 2 times, select [TEETH(FACTOR)], then press [ENTER].
3. Input Teeth number, then press [ENTER].
RUN-STATE OP-
SWITCH
Use / Not use
1. Select [CONTROL] then [ENTER] on Menu screen.
2. Press [▼] 3 times, [▶] 2 times, select [OIL PRESS SENSOR] then [ENTER].
3. Select [Use] then press [ENTER].
1. Select [CONTROL] then [ENTER] on Menu screen.
2. Press [▼] 3 times, [▶] 1 time, select [RUN-STATE OP-GAUGE] then setup oil
pressure.
※ 6.5 Refer to Crank ON/OFF
■ Doosan Engine Gear Teeth
P126TI-3, P126TI, P126TI-II
P158LE-III, P158LE, P158LE-1, P158LE-2, P180LE-II, P158LE, P222LE-1, P222LE,
P222LE-II, P222FE-II
※ Information above written in request of Doosan Commercial Engine(DSCE).
Start motor ON/OFF record stored in ALARM HISTORY.
If start motor is damaged due to ignoring above caution, free A/S from DSCE will NOT be possible