Totalizer Function Overview
When the input is on, if the enable totalizer input (S2) is turned on, totalization starts.
When the enable totalizer input is on, the amount that the flow counter (S1+0, S1+1) increased is added to the
accumulated flow volume work area with each scan. The accumulated time work area count also starts at the same time.
When the enable totalizer input is off, totalization is paused. (The accumulated flow volume work area and the accumulated
time work area values are retained.)
Note: For details on the totalizer function such as the operation immediately after the input is turned on and the operation when the enable totalizer
input is once again turned on, see "Totalizer Function" on page 27-22.
Log Output Function Overview
When the input is on, if the log execution input (S3) is turned on, the logged data (D2) is updated regardless of the enable
totalizer input (S2) on/off status. The maximum amount of logged data is 35 items.
When the enable totalizer input is off, totalization is paused. The accumulated flow volume work area and the accumulated
time work area values are retained.
Note: For details on the log output function such as the operation immediately after the input is turned on, the operation when the enable totalizer
input (S2) is once again turned on, and the logged data updating when the log execution input (S3) is turned on, see "Log Output Function" on page
27-23.
Valid Devices
Special data registers cannot be used.
Device Function I Q M R T C D P Constant Repeat
S1 (Source 1) Flow counter —————— X — — —
S2 (Source 2) Enable totalizer input X — X — — — — — — —
S3 (Source 3) Log execution input X — X — — — — — — —
D1 (Destination 1) Status —————— — — —
D2 (Destination 2) Logged data — — — — — — — — —
Enable totalizer input (S2)
Input
ON
OFF
Flow counter
(
S1+0, S1+1
)
ON
OFF
Accumulated flow volume work area
(system work area)
Accumulated time work area
(system work area)
Enable totalizer input (S2)
Input
ON
OFF
Flow counter
(S1)
ON
OFF
Accumulated flow volume work area
(system work area)
Accumulated time work area
(system work area)
ON
OFF
Log execution input (S3)
Logged data (D2)
Update
Update

Table of Contents

Other manuals for IDEC MICROSmart FC6A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC MICROSmart FC6A Series and is the answer not in the manual?

IDEC MICROSmart FC6A Series Specifications

General IconGeneral
BrandIDEC
ModelMICROSmart FC6A Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals