36 Programming terminals
Centrali anti-intrusione
Table 6-4: Zones - detector type
Zone Generic Roller blind Shock
Control panel terminals
any any any
Expansion terminals
any T1, T2, T3, T4 T1, T2, T3, T4
Keypad terminals
any
any
none for Alien/G
any
none for Alien/G
icon on software
Table 6-5: Zone options
Parameter Software section Installer menu section
Interior
A zone that monitors the inside of the protected
building.
If a partition that a zone belongs to is armed in Stay
mode, it will be unable to generate alarms.
Zones, selected zone,
options
Zones, "zone", Options
Autobypassable
A zone with this attribute will be bypassed
automatically by the control panel if, at the moment
of arming the partitions the zone belongs to, it is not
in stand-by status.
The zone will be unbypassed automatically when it
restores to standby or when the partition it belongs to
is disarms.
Unbypassable
A zone with this attribute cannot be bypassed,
manually (by the user) or automatically (by the
control panel).
Chime
A zone with this attribute will generate “Chime on
partition” events, if violated when the partitions it
belongs to are disarmed.
Keypads which have partitions in common with the
chime zone will emit an audible signal when the
“Chime on partition” event occurs. If all the partitions
the zone belongs to are armed, the zone will operate
as programmed.
Test
A zone with this attribute cannot generate alarms
(activate audible and visual signalling devices).
However, any alarm events that occur will be saved to
the events memory.
No- Unbypass-
able
If this option is enabled, the zone will operate as an
“Autobypassable” zone, with the difference that it will
be automatically unbypassed when the partition next
disarms.
No arm if not
ready
If this option is enabled, the zone, even if it is a 24H,
automation or delayed zone, will not arm when it is
not in stand-by status. If this option is selected for a
24H or technological zone, it can be used together
with the control panel option: “Does not arm if any of
the zones are not ready”, for the management of the
“anti-masking” function on duly capable detectors.
Activate Entry
Time 2
If this option is enabled, delayed zone will activate
the second partition entry time. If this option is not
enabled, delayed zones will activate the first partition
entry time.
Delay time 2
Last exit zone
If this option is enabled and the zone passes from
stand-by status to alarm status while the partition
exit time is running, the exit time will be forced to 15
seconds. If the zone passes from alarm status to
standby status, the exit time will be forced to 5
seconds.
Unbyp. on dis-
arm
If this option is enabled, a zone which has been
bypassed by a user, will be automatically unbypassed
when the partition next disarms.
Hold-up
Activation of a zone with this configuration generates
an instant alarm even when the partition it belongs to
is disarmed. However, audible and/or visual signalling
devices will not be activated (silent alarm). Therefore,
calls generated by the alarm will not be revealed
audibly or visually on the keypad display and LEDs.
Fault zone
If this option is enabled, violation of the zone will
generate a zone alarm event and contribute to fault
signalling (yellow LED on the keypad).