32 Installation
Anti-intrusion control panels
3-1-9
Maintenance status
The maintenance status is signaled on the keypads by the “Maintenance” message and
the address of the keypad. The address of the built-in reader (if enabled) of JOY/MAX
keypads will also be shown.
During service/maintenance mode, the control panel:
• Forces the relay output on the motherboard (Table 2-9: Mother board - terminal
board, 10-11-12) to standby status.
• Does not activate the outputs (and will force to standby any active outputs)
triggered by:
•• alarm or zone/partition tamper
•• peripheral tamper
•• open/dislodged panel tamper
• It allows initialization of the keypad address programming phase.
• It allows initialization of the reader address programming phase.
• Initializes automatically the auto-enrollment of the peripherals connected to the BUS
at 10 seconds intervals. It allows assignment of the addresses to the peripherals
connected to the BUS and, at 10 second intervals, enrolls the peripherals it finds.
• The control panel will not reset the BUS in an attempt to retrieve peripherals in the
event of peripheral loss.
• It will continue to operate as normal, except under the aforesaid circumstances.
During service/maintenance mode, the Alien keypad:
• Does not require user-code entry to access the sections which correspond to the
“Settings” key.
• The first parameters shown in the “Settings - Alien” section are the addresses of the
Alien keypad and its built-in proximity reader and, only for the Alien/S, the status of
tamper enablement on the keypad.
• It is not possible to access the “Climate” section.
• The display shows the address of the Alien keypad and its built-in proximity reader in
the top left-hand corner of the home page.
• The display shows the letters relating to the operating status of the partitions in the
bottom left-hand corner of the home page.
The control panel can be placed in maintenance mode by:
• Inserting the Maintenance jumper in the “SERV” position.
• Enabling the “Maintenance” option
USING THE
MAINTENANCE JUMPER
The Maintenance jumper (Table 2-6: Control panels - description of parts, G) can be
inserted in two different positions:
• “RUN” (control panel operating normally)
• “SERV” (control panel ready for maintenance work)
THE “MAINTENANCE”
OPTION
The control panel enters “Maintenance” mode when this option is enabled and exits
“Maintenance” mode when it is disabled. You can enable/disable this option at the
keypad or via computer.
Via Keypad
1. Access the “Programming Panel options” section.
Type-in Code
(Installer PIN)
, PROGRAMMING Panel options .
2. Press to enable the “Maintenance” option, or to disable it.
3. Press to exit and save.
Via PC
Select “SmartLiving System” from the tree menu on the left, then go to the
“Programming” template on the right: The “Control panel parameters” section provides
the “Maintenance” option, click-on this option to enable/disable it.
Mainten K03 P05