EasyManua.ls Logo

INIM Electronics SmartLiving 10100L - Page 68

INIM Electronics SmartLiving 10100L
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68 Options and programming methods
Anti-intrusion control panels
or
Use keys and to increase or decrease the number.
2. Press to confirm and exit.
Magnetic contact , allows you to change the parameters of an already enrolled
Air2-MC100 magnetic contact. Press , to access the following options:
••
LongSide contact
, detection using the long side of the magnetic contact.
••
ShortSideContact
, detection using the short side of the magnetic contact.
•• Both contacts, detection using both sides of the magnetic contact.
If you select the “Both contacts” option, standby status will be detected when either
(or both) of the 2 reeds close. If you select either “LongSide contact” or
“ShortSideContact”, standby status will be detected when the selected reed closes
and the other opens. If both reeds close, the system will generate a terminal-tamper
event. In fact, the most common method of jamming this type of device is to hold a
magnet in the vicinity of the magnetic contact, should this ever occur, both reed
relays will close to trigger a tamper event.
Terminal T1 M.C. and Terminal T2 M.C., to change the parameters of terminal
“T1” of an enrolled Air2-MC100. If you press at this point, the keypad will step
back to the Zones menu and you can set up the parameters of the terminal:
Balancing, Rollerblind, Times, etc.
Terminals “T1” and/or “T2” of the Air2-MC100 device can be set up in the same way
as wired terminals, with the exception that wireless terminals cannot be configured
as “double zones”.
Magn.Cont. MC200, allows you to change the parameters of an already enrolled
MC200 magnetic contact. Press
to access the following options:
••
Infrared Shock
- allows you to set the sensitivity of the shock sensor (set “0” to disable,
“1” for minimum sensitivity and “63” for the maximum sensitivity).
••
Tilt
- allows you to set the maximum angle allowed before signalling of tilting occurs.
•• Tilt duration, allows you to set the signal delay after the detection of tilting
(variation of the angle).
If shock and tilt detection are both enabled, alarm signalling will be generated as
soon as one of these conditions exceeds its set value.
Curtain detector,
Dual T detector,
Single T detector,
Outdoor detector,
these items display the same menu that appears when is pressed:
••
Sensitivity
- allows you to set the sensitivity of the PIR detector
••
Shock Sensit. -
allows you to set the sensitivity of the shock detector
••
Microwave Sensit.
- allows you to set the sensitivity of the microwave sensor
••
Antimask Sensit.
- allows you to set the sensitivity of the antimasking mechanism
The previously mentioned parameters will be shown in accordance with the specific
device type. The values can be “0” for disablement, “1” for minimum value and “15”
for maximum value.
Alarm signalling will occur as soon as one of the two sensors exceeds its
programmed alarm threshold.
Balancing
Balancing can be (refer to Appendix A, Technical terminology and Glossary and
paragraph 3-5 Wiring and balancing alarm detectors):
Norm. open (NO)
Norm.closed (NC)
Single balancing
Double balancing
Double Zone (without EOL)
Double Zone EOL (with EOL)
Alarm cycles
This programmable parameter accepts values between 1 and 15. If you set the value at
15, the zone will operate as a “repetitive zone” (refer to Appendix A, Technical
terminology and Glossary, Alarm cycles).
Detector type
It is possible to configure a zone as:
Generic zone
Rollerblind
•Shock
The following Table shows the terminals which accept Generic, Rollerblind and Shock
zones, and the respective zone-parameter fields for each type.

Table of Contents

Other manuals for INIM Electronics SmartLiving 10100L

Related product manuals