EasyManua.ls Logo

INIM Electronics SmartLiving 10100L - Page 69

INIM Electronics SmartLiving 10100L
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and programming manual
Options and programming methods 69
Al. pulse Duration (generic zone)
This is the length of time (after detection of alarm conditions) the zone allows before
generating an alarm. Expressed in multiples of 15 milliseconds or 10 seconds.
Multipulse time (generic zone)
This parameter applies only when the “Alarm pulse num." parameter is more than 1.
This is the window during which a number of alarm pulses must be detected (each
lasting as long as the programmed “Al.pulse Duration”). The number of alarm pulses
must equal or exceed the value programmed for “Alarm pulses”, before the system
generates an alarm. This window can be expressed in seconds or minutes (see
opposite).
Alarm pulse num. (generic zone)
This is the number of pulses (each lasting as long as the programmed “Al.pulse
Duration”) necessary to generate a zone alarm event. If this value is more than 1, you
must also programme the “Multipulse time” parameter.
Rollerblind time (rollerblind zone)
This parameter applies only when the value of the “Rollerbl. pulses” (see below) is more
than 1.
This is the time window during which the system must detect a number of pulses equal
to or higher than the value programmed for “Rollerbl. pulses” before generating a zone
alarm. This window can be expressed in seconds or minutes (see opposite).
Rollerbl. pulses (rollerblind zone)
This is the number of pulses necessary to generate a zone-alarm event. If this value is
more than 1, you must also programme the “Rollerblind time” parameter.
Shock sensit. (shock zone)
This is an empirical parameter which regulates the sensitivity of the sensor. Increasing
this value decreases detection sensitivity.
Shock time (shock zone)
This parameter applies only when the “Shock pulses” value is more than 1.
This is the window during which a number of pulses must be detected the number of
alarm pulses must equal or exceed the value programmed for “Shock pulses”, before
the system generates an alarm. This window can be expressed in seconds or minutes
(see opposite).
Shock pulses (shock zone)
This is the number of pulses necessary to generate a zone-alarm event.
If this value is more than 1, you must also programme the “Shock time” parameter.
If this value is 0, the zone alarm will be generated by the “Shock sensit.” parameter.
All the above-mentioned values can be programmed as follows:
1. Use and where possible to indicate the time in multiples of 15
millieseconds, seconds or minutes (refer to the note opposite).
2. Use keys and to select the field you wish to change, then use the number
keys ( , etc.) to edit the number.
or
Use keys and to increase or decrease the number.
3. Press to confirm and exit.
Via PC
Programming zones via the SmartLeague application is accomplished by the selection
and programming of the terminal configured as zone, described in paragraph 7-6
Terminals.
Table 7-4:
Zone - detector type
Generic zone Rollerblind Shock
Control panel terminals
any T1, T2 T1, T2
Expansion terminals
any T1, T2, T3 or T4 T1, T2, T3 or T4
Keypad terminals
any any any
Extra Parameters
Al. pulse Duration
Multipulse time
Alarm pulses
Rollerblind time
Rollerbl. pulses
Shock sensit.
Shock time
Shock pulses
If this value is
expressed in
minutes, there is an
error margin of one
minute (for example, if you
set 5 minutes, the effective
period can vary between 4
and 5 minutes).

Table of Contents

Other manuals for INIM Electronics SmartLiving 10100L

Related product manuals