Appendix. Parameter Table
- 318 -
Parameter
No.
Parameter Name Setting Range Default Property Page
F8-48 Cooling fan working mode 0, 1 0
☆
1
9
9
F8-49 Wakeup frequency F8-51 to max. frequency
(F0-10)
0.00 Hz
☆
2
0
0
F8-50 Wakeup delay time 0.0s to 6500.0s 0.0s
☆
2
0
0
F8-51 Hibernating frequency 0.00 Hz to wakeup frequency
(F8-49)
0.00 Hz
☆
2
0
0
F8-52 Hibernating delay time 0.0s to 6500.0s 0.0s
☆
2
0
0
F8-53 Running time threshold this time 0.0 to 6500.0 min 0.0 min
☆
2
0
0
F8-54 Output power correction
coefcient
0.0% to 200.0% 100.0%
☆
2
0
0
F8-55 Deceleration time for emergency
stop
0s to 6553.5s Model
dependent
☆
2
0
0
Group F9: Fault and Protection
F9-00 Motor overload protection 0, 1 1
☆
1
3
9
F9-01 Motor overload protection gain 0.20 to 10.00 1.00
☆
1
3
9
F9-02 Motor overload pre-warning
coefcient
50% to 100% 80%
☆
1
4
0
F9-03 Overvoltage protection gain 0 (no overvoltage stall) to
100
30
☆
1
3
3
F9-04 Overvoltage protection voltage 650 to 800 V 770 V
☆
1
3
3
F9-07 Detection of short-circuit to ground
upon power-on
00 to 11 01
☆
-
F9-08 Braking unit applied voltage 650 to 800 V 760 V
★
1
3
3
F9-09 Auto reset times 0 to 20 0
☆
1
4
1
F9-10 Selection of DO action during auto
reset
0, 1 0
☆
1
4
1
F9-11 Delay of auto reset 0.1s to 100.0s 1.0s
☆
1
4
1
F9-12 Input phase loss/pre-charge relay
protection
00 to 11 11
☆
1
4
0
F9-13 Output phase loss protection 00 to 11 01
☆
1
4
0
F9-14 1st fault type 0 to 55 - ● -
F9-15 2nd fault type 0 to 55 - ● -
F9-16 3rd (latest) fault type 0 to 55 - ● -
F9-17 Frequency upon 3rd fault - - ● -
F9-18 Current upon 3rd fault - - ● -
F9-19 Bus voltage upon 3rd fault - - ● -
F9-20 DI state upon 3rd fault - - ● -
F9-21 DO state upon 3rd fault - - ● -
F9-22 AC drive state upon 3rd fault - - ● -
F9-23 Power-on time upon 3rd fault - - ● -
F9-24 Running time upon 3rd fault - - ● -
F9-27 Frequency upon 2nd fault - - ● -
F9-28 Current upon 2nd fault - - ● -