Goodrive350 IP55 High-ingress Protection Series VFD Basic Operation Instructions
-97-
Digital output 16
Simple PLC state completed
Digital output 17
Simple PLC cycle completed
Related parameter list:
Function
code
Name
Description
Default
value
P05.01
P05.06
Digital input function
23: Simple PLC stop reset
24: Simple PLC pause
25: PID control pause
P06.01
P06.04
Digital output function
16: Simple PLC stage reached
17: Simple PLC cycle reached
P10.00
Simple PLC mode
0: Stop after running once
1: Keep running in the final value after
running once
2: Cyclic running
0
P10.01
Simple PLC memory
selection
0: No memory after power down
1: Memory after power down
0
P10.02
Multi-step speed 0
-300.0300.0%
0.0%
P10.03
Running time of 0
th
step
0.06553.5s (min)
0.0s
P10.04
Multi-step speed 1
-300.0300.0%
0.0%
P10.05
Running time of 1
st
step
0.06553.5s (min)
0.0s
P10.06
Multi-step speed 2
-300.0300.0%
0.0%
P10.07
Running time of 2
nd
step
0.06553.5s (min)
0.0s
P10.08
Multi-step speed 3
-300.0300.0%
0.0%
P10.09
Running time of 3
rd
step
0.06553.5s (min)
0.0s
P10.10
Multi-step speed 4
-300.0300.0%
0.0%
P10.11
Running time of 4
th
step
0.06553.5s (min)
0.0s
P10.12
Multi-step speed 5
-300.0300.0%
0.0%
P10.13
Running time of 5
th
step
0.06553.5s (min)
0.0s
P10.14
Multi-step speed 6
-300.0300.0%
0.0%
P10.15
Running time of 6
th
step
0.06553.5s (min)
0.0s
P10.16
Multi-step speed 7
-300.0300.0%
0.0%
P10.17
Running time of 7
th
step
0.06553.5s (min)
0.0s
P10.18
Multi-step speed 8
-300.0300.0%
0.0%
P10.19
Running time of 8
th
step
0.06553.5s (min)
0.0s
P10.20
Multi-step speed 9
-300.0300.0%
0.0%
P10.21
Running time of 9
th
step
0.06553.5s (min)
0.0s
P10.22
Multi-step speed 10
-300.0300.0%
0.0%
P10.23
Running time of 10
th
step
0.06553.5s (min)
0.0s