EasyManuals Logo

INVT Goodrive350 IP55 User Manual

INVT Goodrive350 IP55
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #83 background imageLoading...
Page #83 background image
Goodrive350 IP55 High-ingress Protection Series VFD Basic Operation Instructions
-74-
Function
code
Name
Description
Default
value
P08.19
Switching frequency of
acceleration/deceleration
time
0.00–P00.03 (max. output frequency)
0.00Hz: No switch over
If the running frequency is larger than
P08.19, switch to acceleration
/deceleration time 2
0
P08.21
Reference frequency of
acceleration/deceleration
time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note: Valid for straight-line
acceleration/deceleration only
0
P08.28
Automatic fault reset times
0–10
0
P08.29
Automatic fault reset time
interval
0.1–3600.0s
1.0s
5.5.8 Frequency setup
The VFD supports multiple kinds of frequency reference modes, which can be categorized into
two types: main reference channel and auxiliary reference channel.
There are two main reference channels, namely frequency reference channel A and frequency
reference channel B. These two channels support simple arithmetical operation between each
other, and they can be switched dynamically by setting multi-function terminals.
There is one input mode for auxiliary reference channel, namely terminal UP/DOWN switch
input. By setting function codes, users can enable the corresponding reference mode and the
impact made on the VFD frequency reference by this reference mode.
The actual reference of VFD is comprised of the main reference channel and auxiliary
reference channel.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive350 IP55 and is the answer not in the manual?

INVT Goodrive350 IP55 Specifications

General IconGeneral
BrandINVT
ModelGoodrive350 IP55
CategoryMedia Converter
LanguageEnglish

Related product manuals