Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-150-
Function
code
Name
Description
Default
value
Modify
77: Clear alarm display
78: Manual braking
79: Trigger forced feeding interrupt
80: Initial roll diameter 1
81: Initial roll diameter 2
82: Trigger fire mode control
83: Switch tension PID parameters
8495: Reserved
P05.07
Reserved
/
/
/
P05.08
Polarity of
input terminal
This function code is used to set the polarity of
input terminals.
When the bit is set to 0, input terminal polarity is
positive;
When the bit is set to 1, input terminal polarity is
negative;
0x0000x3F
0x000
P05.09
Digital filter
time
Set S1S4, filter time of HDI terminal sampling. In
cases where interference is strong, increase the
value of this parameter to avoid mal-operation.
0.0001.000s
0.010s
P05.10
Virtual
terminal
setting
0x000x3F (0: disable, 1: enable)
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: HDIA virtual terminal
BIT5: HDIB virtual terminal
0x00
P05.11
2/3 wire
control mode
This function code is used to set the 2/3 wire
control mode.
0: 2-wire control 1; integrate enabling function with
direction. This mode is the most popular dual-line
mode. Direction of motor rotation is determined by
the defined FWD/REV terminal command.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF OFF
OFF
OFF
ON
ON
ON ON
Stop
Hold
Forward
running
Reverse
running
1: 2-wire control 2; separate enabling function with
direction. In this mode, the defined FWD is
enabling terminal, and the direction is determined
by the state of REV.
0