Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-204-
Function
code
Name
Description
Default
value
Modify
P17.34
Torque current
reference
Display torque current reference value under
vector control mode
Range: -3000.03000.0A
0.0A
P17.35
AC incoming
current
Display the valid value of incoming current on
AC side
Range: 0.05000.0A
0.0A
P17.36
Output torque
Display output torque value, during forward
running, positive value is motoring state,
negative value is generating state; during
reverse running, positive value is generating
state, negative value is motoring state.
Range: -3000.0Nm3000.0Nm
0.0Nm
P17.37
Motor overload
count value
065535
0
P17.38
Process PID
output
-100.0%100.0%
0.00%
P17.39
Parameter
download wrong
function code
0.0099.00
0.00
P17.40
Motor control
mode
0x0000x123
Ones: Control mode
0: Vector 0
1: Vector 1
2: VF control
3: Closed-loop vector control
Tens: Control state
0: Speed control
1: Torque control
2: Position control
Hundreds: Motor number
0: Motor 1
1: Motor 2
0x000
P17.41
Upper limit of the
torque when
motoring
0.0%300.0% (rated motor current)
180.0%
P17.42
Upper limit of
brake torque
0.0%300.0% (rated motor current)
180.0%
P17.43
Upper limit
frequency of
forward running of
torque control
0.00P00.03
50.00Hz
P17.44
Upper limit
frequency of
reverse running of
torque control
0.00P00.03
50.00Hz
P17.45
Inertia
-100.0%100.0%
0.0%

Table of Contents

Related product manuals