Goodrive350 IP55 High-ingress Protection Series VFD Basic Operation Instructions
-47-
Function
code
Name
Description
Default
value
P00.18
Function parameter
restoration
0: No operation
1: Restore to default value
2: Clear fault records
3: Reserved
4: Reserved
5: Restore default values (for factory test
mode)
6: Restore default values (including motor
parameters)
Note: After the selected function operations
are done, this function code will be restored to
0 automatically. Restoration to default value
will clear the user password. Excesise in
caution. The option 5 can be used only for
factory testing.
0
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
P02.01
Rated power of
asynchronous motor 1
0.13000.0kW
Depend on
model
P02.02
Rated frequency of
asynchronous motor 1
0.01HzP00.03 (max. output frequency)
50.00Hz
P02.03
Rated speed of
asynchronous motor 1
160000rpm
Depend on
model
P02.04
Rated voltage of
asynchronous motor 1
01200V
Depend on
model
P02.05
Rated current of
asynchronous motor 1
0.86000.0A
Depend on
model
P02.15
Rated power of
synchronous motor 1
0.13000.0kW
Depend on
model
P02.16
Rated frequency of
synchronous motor 1
0.01HzP00.03 (max. output frequency)
50.00Hz
P02.17
Number of pole pairs of
synchronous motor 1
150
2
P02.18
Rated voltage of
synchronous motor 1
01200V
Depend on
model
P02.19
Rated current of
synchronous motor 1
0.86000.0A
Depend on
model
P05.01
P05.06
Function of multi-function
digital input terminal
(S1S4, HDIA, HDIB)
36: Command switches to keypad
37: Command switches to terminal
38: Command switches to communication
/

Table of Contents