EasyManua.ls Logo

INVT Goodrive350 IP55 - Page 75

INVT Goodrive350 IP55
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350 IP55 High-ingress Protection Series VFD Basic Operation Instructions
-66-
Related parameter list:
Function
code
Name
Description
Default
value
P00.01
Running command channel
0: Keypad
1: Terminal
2: Communication
0
P00.15
Motor parameter autotuning
0: No operation
1: Rotary autotuning 1; carry out
comprehensive motor parameter
autotuning; rotary autotuning is used in
cases where high control precision is
required;
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load;
3: Static autotuning 2 (partial autotuning) ;
when current motor is motor 1, only
P02.06, P02.07 and P02.08 will be
autotuned; when current motor is motor 2,
only P12.06, P12.07 and P12.08 will be
autotuned.
4: Rotary autotuning 2, which is similar to
rotary autotuning 1 but is only applicable to
asynchronous motors.
5: Rotary autotuning 3 (partial autotuning),
which is only applicable to asynchronous
motors.
0
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
P02.01
Rated power of
asynchronous motor 1
0.13000.0kW
Depend on
model
P02.02
Rated frequency of
asynchronous motor 1
0.01HzP00.03 (max. output frequency)
50.00Hz
P02.03
Rated speed of
asynchronous motor 1
160000rpm
Depend on
model
P02.04
Rated voltage of
asynchronous motor 1
01200V
Depend on
model
P02.05
Rated current of
asynchronous motor 1
0.86000.0A
Depend on
model
P02.06
Stator resistance of
asynchronous motor 1
0.001–65.53
Depend on
model
P02.07
Rotor resistance of
asynchronous motor 1
0.001–65.53
Depend on
model
P02.08
Leakage inductance of
asynchronous motor 1
0.16553.5mH
Depend on
model
P02.09
Mutual inductance of
asynchronous motor 1
0.16553.5mH
Depend on
model

Table of Contents

Related product manuals