Goodrive350 IP55 High-ingress Protection Series VFD Basic Operation Instructions
-77-
Reference object of B
frequency command
0: Max. output frequency
1: A frequency command
Combination mode of setup
source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max (A, B)
5: Min (A, B)
Function of multi-function
digital input terminal (S1–S4,
HDIA, HDIB)
10: Frequency increase (UP)
11: Frequency decrease (DOWN)
12: Clear frequency increase/decrease
setting
13: Switch-over between setup A and
setup B
14: Switch-over between combination
setup and setup A
15: Switch-over between combination
setup and setup B
0x000–0x221
Ones: Frequency enabling selection
0: UP/DOWN terminal setting is valid
1: UP/DOWN terminal setting is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: Valid for all frequency modes
2: Invalid for multi-step speed when
multi-step speed takes priority
Hundreds: Action selection at stop
0: Valid
1: Valid during running, clear after stop
2: Valid during running, clear after
receiving stop command
UP terminal frequency
incremental change rate
DOWN terminal frequency
decremental change rate
0.00Hz–P00.03 (max. output frequency)
Ramps reference frequency
0.00Hz–P00.03 (max. output frequency)