EasyManuals Logo

Johnson Controls LSWU035 User Manual

Johnson Controls LSWU035
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #199 background imageLoading...
Page #199 background image
JOHNSON CONTROLS
199
SECTION 8 – SERVICE
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
8
Flash Code 6 – Discharge Thermistor
Fault
This code indicates the Digital Compressor Controller
is not receiving a signal from the discharge tempera-
ture thermistor. If the Digital Compressor Controller is
not receiving an input signal it continues to operate the
compressor at 1/3 capacity. When the discharge tem-
perature thermistor input is restored the Digital Unit
Controller resumes normal operation.
Flash Code 8 – Compressor Contactor
Fault
This code indicates compressor current is detected
when the demand signal input is below 1.44VDC. This
would normally be caused by welded contactor con-
tacts. The compressor continues to run in this condi-
tion because the Digital Compressor Controller cannot
open the compressor contactor.
The Digital Compressor Controller energizes the com-
pressor contactor. The unloader solenoid remains ener-
gized causing the compressor to run unloaded as long
as the input demand signal is less than 1.44VDC. If the
demand input is greater than 1.44VDC, the unloader
solenoid de-energizes causing the compressor to run
loaded.
The ALERT code is reset when current is no longer
detected while the demand input is below 1.44VDC.
Flash Code 9 – Low 24VAC Supply
This indicates the supply voltage to the Digital Com-
pressor Controller has dropped below 18.5VAC. The
Digital Compressor Controller de-energizes the com-
pressor contactor and unloader solenoid. The ALERT
code resets when the supply voltage to the Digital
Compressor Controller rises above 19.5VAC.
FAULTS
A fault is defined as an abnormal condition, which
results in the shutdown of an operating system or the
complete unit. The presence of a fault condition indi-
cates a situation in which possible damage to the unit
may occur if the unit or system were allowed to con-
tinue to operate. There are four types of faults.
UNIT LOCKOUT – The complete unit is shut-
down and locked out. A manual reset is required
to restart the unit after the fault has been corrected.
SYSTEM LOCKOUT – One of the compres-
sor systems or other component is shutdown and
locked out. A manual reset is required to restart
the system after the fault has been corrected.
UNIT AUTO RESET – The complete unit is shut-
down but the unit restarts automatically when the
fault condition is cleared.
SYSTEM AUTO RESET – One of the compres-
sor systems or other component is shut down but
the system or component restarts automatically
when the fault condition is cleared.
A UNIT LOCKOUT can be reset by turning the “LO-
CAL STOP” switch OFF for 5 seconds and back ON.
If the cause of the lockout has been corrected the unit
resets and begins proper operation.
A SYSTEM LOCKOUT except for COMPR # LOCK-
OUT and LOCKOUT - LOW PRESS SYS # can be
reset by turning the “LOCAL STOP” switch OFF for
5 seconds and back ON. A COMPR # LOCKOUT and
LOCKOUT - LOW PRESS SYS # must be reset by
entering the PROGRAM key and the COMPRESSOR
SYSTEMS # subsection, which has the lockout. Use
the and key to go to COMP SYS # STATE. The
current status is LOCKOUT. Press the CHECK key (√)
and use the right arrow key to change LOCKOUT to
RUN.
In addition to faults the User Interface also displays
warnings. A warning is defined as an abnormal condi-
tion under which the unit continues to operate. Warn-
ings do not require the unit to shut down; however,
they may require the Unit Controller to disable certain
functions that may result in the unit operating less ef-
ficiently or eliminate certain features.
Table 50 on page 205, Table 51 on page 206 and
Table 52 on page 207 list the faults / warnings that
are displayed under the STATUS and HISTORY keys
of the User Interface. When a fault is present line
two of the effected STATUS screen display (UNIT-
OVERALL STATUS, COMPRESSOR SYSTEM
A, COMPRESSOR SYSTEM B, COMPRESSOR
SYSTEM C, COMPRESSOR SYSTEM D, COM-
PRESSOR SYSTEM E, COMPRESSOR SYSTEM
F, HEATING SYSTEM, ECONOMIZER SYSTEM,
SUPPLY SYSTEM or VENTILATION SYSTEM)
changes the nomenclature to indicate a WARN-
ING, SAFETY TRIP, SAFETY FAULT, or SAFETY
LOCKOUT is present. A fault / warning description,
method of reset and conditions under which the infor-

Table of Contents

Other manuals for Johnson Controls LSWU035

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls LSWU035 and is the answer not in the manual?

Johnson Controls LSWU035 Specifications

General IconGeneral
BrandJohnson Controls
ModelLSWU035
CategoryChiller
LanguageEnglish

Related product manuals