iSTAR Edge G2 Controller Installation and Configuration Guide 42
Chapter 5 - Controls and Displays
Output Relay (Wet or Dry Jumper)
The four output relays can be Dry or Wet based on the position of the jumpers.
When Dry the integrator must supply the external power that the relay switches. When set to Dry, use the C, NO, and
NC connections.
When Wet the iSTAR Edge G2 sources the power. When set to Wet, use the GND, NO, and NC connections. Be sure
to stay within the power budget when using the Wet setting and powering by PoE.
For more information, see Chapter 6: Connections.
PoE or PoE+ Jumpers
The PoE board has a set of 4 jumper locations. The right-most jumper location indicates PoE+ and the one left of it indicates
PoE. Put the one jumper on the appropriate location.
There is also a jumper to select whether the PoE board supplies 12VDC or 24 VDC to the iSTAR Edge G2. The jumper must be
configured for 24VDC.For more information, see Chapter 4: Power and Backup.
C•CURE 9000 Status Tab
The C•CURE 9000 Controller Status tab indicates the iSTAR Edge G2 Model, whether a PoE board is installed, and other
information about the state of the iSTAR Edge G2.