LI - Input Parameters
LI03 = D(Level - High - Inspect. - Interm.) [Leveling at start], NUM = 4
US04
Digital Speed
Selection
Param. Control Inputs
I1 I2 I3 I4
S
ZERO
- 0 0 0 0
S
LEVELING
LS01 1 0 x x
S
HIGH SPEED
*
LS02 1 1 x x
S
HIGH SPEED
LS02 0 1 x x
S
INSPECTION
LS03 0 0 1 x
S
INTERMEDIATE 1
LS05 0 0 0 1
* Valid only at start (once leveling speed is reached it is not possible
to accelerate up to high speed again until after zero speed has been
selected)
LI03 = D(Inspect. - Level - High - Interm.), NUM = 8
US04
Digital Speed
Selection
Param. Control Inputs
I1 I2 I3 I4
S
ZERO
- 0 0 0 0
S
LEVELING
LS01 0 1 x x
S
HIGH SPEED
LS02 0 0 1 x
S
INSPECTION
LS03 1 x x x
S
INTERMEDIATE 1
LS05 0 0 0 1
LI03 = D(Level - Int.2 - High - Inspect), NUM = 12
US04
Digital Speed
Selection
Param. Control Inputs
I1 I2 I3 I4
S
ZERO
- 0 0 0 0
S
LEVELING
LS01 1 0 x x
S
HIGH SPEED
LS02 0 0 1 x
S
INSPECTION
LS03 0 0 0 1
S
INTERMEDIATE 1
LS05 1 1 0 x
S
INTERMEDIATE 2
LS06 0 1 x x
Symbol: 1 = Input is active
0 = Input is not active
x = Setting has no effect or doesn’t care

Table of Contents

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
CategoryDC Drives
Enclosure RatingIP20
Control ModeVector Control, V/f Control
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Fieldbus CommunicationPROFIBUS, CANopen
Communication InterfacesRS-485
Input Voltage380-480V AC
Cooling MethodForced air cooling (fan)

Related product manuals