Component Description
October 2014 3-2 06-236115-001
3-2 FUNCTIONAL DESCRIPTION
Compressed HFC-227ea liquid is held in the agent storage container by a discharge valve.
When the discharge valve is actuated, the compressed liquid agent discharges through the
valve outlet and is directed through the distribution piping to the nozzles. The nozzles provide
the proper flow rate and distribution of HFC-227ea.
The Kidde ECS System is composed of the following components and assemblies:
Cylinder/valve assembly
Liquid level indicator (optional)
Control head (electric, cable operated, lever operated, pressure operated and electric and
cable operated)
•Pressure gauge
Straps and brackets for mounting the cylinder
Cable manual pull station
Nitrogen actuator and mounting bracket
Actuation hose
Flexible discharge hose
Master cylinder adapter kit
Tees, elbows and adapters
•Check valve
Valve outlet adapter
Discharge nozzle
Discharge indicator
•Corner pulley
Supervisory pressure switch (optional)
Hydrostatic test adapter
HFC-227ea cylinder recharge adapter
HFC-227ea cylinder seating adapter
Main to reserve transfer switch
•Manifold El-check
•Detector
Pressure operated switch and trip
•Control panel
Figure 3-1 and Figure 3-2 show the above components in two typical configurations.