Design and Installation
06-236115-001 4-7 October 2014
4-2.2.3 Determine What Components are Required
Cylinder size, quantity and fill requirements. Refer to Table 4-4 and Table 4-5.
Cylinder framing, mounting brackets, etc.
Detection and control equipment required.
Other system requirements, such as reserve supply, pressure switches, etc.
4-2.2.4 Locate Nozzles
Locate nozzles based on the following:
Ceiling height (16 ft [4.87 m] maximum, 1 ft [0.30 m] minimum).
Nozzle area coverage.
Special hazard area layout considerations.
4-2.2.5 Locate Cylinders
Locate cylinders based on the following:
Number of cylinders required.
Storage temperature/environmental considerations, such as weather, area classification
and corrosive environment.
Accessibility.
Floor loading.
4-2.2.6 Locate Piping
Locate piping based on the following:
Nozzle location.
Structural members for bracing the pipe.
4-2.2.7 Pipe Size and Layout
Determine pipe size and layout for the following factors:
Draw piping isometric.
Dimensions of all pipe sections.
Locate all fittings.
Note all elevation changes.
The preceding information will be entered into the computer program.