Design and Installation
October 2014 4-14 06-236115-001
Figure 4-4. Nozzle Limitations
Note: Any system designed for a space less than 12 in (0.3 m) in height is not a UL Listed or
FM Approved design.
4-2.3.6 Pipe Sizing
The following table may be used as an estimating guide for sizing distribution piping.
Note: This table is intended for use as a guide only. The latest version of the flow calculation
software program must be used for the final design.
Table 4-7. Kidde Pipe Size Estimating Table
Nominal Pipe Size
(inches)
Flow Rate (lb/sec) Flow Rate (kg/s)
Minimum Design Max. Nom. Design Minimum Design Max. Nom. Design
1/2 1 3.0 0.5 1.4
3/4 2 5.5 0.9 2.5
1 3.5 8.5 1.6 3.9
6 12.5 2.7 5.7
9 20.0 4.1 9.0
2 14 30.0 6.4 13.6
20 55.0 9.0 25.0
3 30 90.0 13.6 40.9
4 55 125.0 25 56.8
5 90 200.0 40.9 90.9
6 120 300.0 54.5 136.4
30ft. Max
30 ft. Max
System With A
Single Row of Nozzles
System With A
Multiple Row of Nozzles
30 ft. Max
System With Ceiling
and Subfloor Nozzles

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde Fire Systems ECS and is the answer not in the manual?

Kidde Fire Systems ECS Specifications

General IconGeneral
BrandKidde Fire Systems
ModelECS
CategoryFire Extinguisher
LanguageEnglish

Related product manuals