REMOVAL FROM SERVICE
1. Remove all control heads, pressure operated heads, and pilot loops from cylinder valve, and attach
protection cap to actuation port.
2. Disconnect cylinders from system piping at the valve outlet. Disconnect valve outlet
adapter, if used.
3. Immediately install safety cap on valve outlet.
4. Remove cylinder from bracketing.
WARNING
Do not disconnect the cylinder from system piping if the safety cap is missing. Obtain a
new safety cap from Kidde.
WARNING
Failure to follow these instructions, and improper use or handling, may cause serious
bodily injury, death, and property damage.