EasyManua.ls Logo

LEGRAND 3440 - Page 492

LEGRAND 3440
518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
483
OUT
I N
C
I1 =
I2 =
I3 = 3
I4 = 2
MOD
= 1
OUT
I N
C
I1 =
I2 =
I3 = 7
I4 = 7
MOD
= 1
OUT
I N
C
I1
=
I2
=
I3
=
5
I4
=
4
MOD =
1
OUT
IN
OUT
IN
OUT
IN
F422
Installation example
Installation rules:
- Configure both I3 and I4 with configurators from 1 to 9, to set the separation between
the two Buses.
- I1 and I2 must not be configured.
- If several interfaces are installed in series, the addresses of the devices between one in-
terface and the other must be within those of the two interfaces (see system example).
- In this mode, it is not possible to install two interfaces in parallel on the same BUS.
- It is possible to install up to four interfaces in series, which subdivide the system in 5
separate sections, individually powered.
- The scenario module, the memory module, the IR emitter for the control of air con-
ditioning units, and the devices that can be configured in self-learning mode, must
be installed on the BUS section corresponding to the own local address (e.g. if the
scenario module is configured as A=0/PL=1, it will have to be placed on system
no. 1 - see system example).
- The web server and the scenario programmer must be installed on the BUS line with the
lowest addresses (system 1 on the drawing).
- All control devices configured for sending Point-Point, Room, Group, and General con-
trols may be connected to any branch of the system (no.1 or no. 2), without limitation,
irrespective of their respective addresses in the A and PL positions.
- The above also applies to actuators configured in slave operating mode.
- Interface F422 allows Point-Point, Group, Room, and General controls to travel through
the various systems. It is therefore possible to install, for example, in system no. 2 a
control configured as A=1 and PL=5 that will control actuator A=1 and PL=5 installed
in system no. 1.
- Within the system, no device must be configured with the same address as the interface.
1
3
A/PL = 55 76
Automation
2 4
A/PL = 33 53 A/PL = 78 175 (*)
Automation Automation
A/PL = 01 31
Automation
Note (*): maximum number of addresses available with virtual configuration of the devices.
1
MQ00280-e-EN 07/06/2014
SCS/SCS
gateway

Related product manuals