067226 HD/HC/HS4658
L/N/NT4658N
574048
574098 AM5658
This devices features a PIR and US (ultrasound) movement detector, and a brightness
sensor for automatic activation of various types of loads following the detection of a
movement, and a brightness level lower than the set level.
The enabling/disabling of the load can also be performed manually using the
appropriate front pushbutton and/or using an external BUS control device.
IT is possible to configure several operating modes; for the detailed descriptions see
page 4.
Description
1. PIR sensor
2. LEARN LED
3. US sensor
4. ON-OFF button
5. LEARN button
6. Movement detector sensor (under the lens)
7. Infrared transmitter (under the lens)
8. Brightness sensor
Voltage: 27 V=
Current draw: 17 mA
Connection between sensor and actuator: SCS BUS connector
Sensor type: movement detector (PIR+US) with 180°
detection angle and brightness sensor.
Flush mounted box depth: 40 mm
Weight: 60 g
Impact resistance: IK04
Penetration of solids and liquids: IP20
Time delay: from 5 sec to 59 min. 59 sec
Brightness: from 20 lux to 1275 lux
Operating temperature: from - 5 °C to + 45 °C
Storage temperature: from - 20 °C to + 70 °C
Technical data
Dimensional data
Front view
Legend
Size: 2 flush mounted modules
A B C
45 45 51
PIR+US ush-mounted SCS Green Switch
MQ00473-f-EN 09/06/2014
Standards, Certifications, Marks
Directive:
– Electromagnetic Compatibility Directive 2004/108/EC
Installation regulations:
– CEI 64-8
Product regulations:
– IEC 60669-2-1
– EN 50428
Environmental regulations:
– EU Directive 2002/96/EC: WEEE (Waste Electrical and Electronic Equipment)
– EU Directive 2002/95/EC: RoHS (Restriction of Hazardous Substances)