b.Slightlypresstheretentionclipoutwardtoremovethebatteryorpowermodule.
Tab
Battery / flash power module
4
Figure44.RAIDadapterbatteryorflashpowermoduleremovalfor3.5-inchharddiskdriveservermodels
IfyouareinstructedtoreturntheRAIDadapterbatteryorflashpowermodule,followallpackaging
instructions,anduseanypackagingmaterialsforshippingthataresuppliedtoyou.
ReplacingaRAIDadapterbatteryorflashpowermodule
UsethisinformationtoreplaceaRAIDadapterbatteryorflashpowermodule.
WhenyouinstallanyRAIDadapterthatcomeswithbatteriesorflashpowermodules,itissometimes
necessarytoinstallthebatteriesorflashpowermodulesinanotherlocationintheservertopreventthe
batteriesorflashpowermodulesfromoverheating.Dependingonyourservermodel,abatteryorflash
powermodulemustbeinstalledremotelyneartheopticaldrivecageorthebackplane.
ToinstallaRAIDadapterbatteryintheserver,completethefollowingsteps:
Note:The2.5-inchharddiskdriveservermodelsupportsuptotwoRAIDadapterbatteriesorflash
powermodules,whilethe3.5-inchharddiskdriveservermodelsupportsonlyoneRAIDadapterbattery
orflashpowermodule.
Step1.Readthesafetyinformationthatbeginson“Safety”onpagevand“Installationguidelines”on
page116.
Step2.Turnofftheserverandperipheraldevicesanddisconnectallpowercordsandexternaldevices.
Step3.Removethecover(see“Removingthecover”onpage119).
Step4.InstalltheServeRAIDadapteronthesystemboard(see“ReplacingaServeRAIDSAS/SATA
controller”onpage185)orinstalltheServeRAIDadapterontherisercardandinstalltheriser-card
assemblyintheserver(see“Replacinganadapter”onpage178and“ReplacingaPCIriser-card
assembly”onpage172
).
Step5.ConnectoneendofthecabletotheRAIDadaptermemorymodule.
Chapter5.Removingandreplacingcomponents127