38
ENGLISH
USING THE PROGRAM
Air-cooled scroll chiller, water-cooled scroll chiller
Air-cooled and water-cooled is separated according to the refrigerant (cooling in air: air, liquid-
cooled: water). Functions and menus are the same, but there is a difference in the range and set
temperature, etc.
The following menu controls the configuration and function of the air-cooled scroll chiller, water-
cooled scroll chiller.
Item Description
Operation
y [ON] Button: Starts the operation of the device.
y [OFF] Button: Stops the operation of the device.
GoTo
y [Schedule ] Button: Move to Schedule menu.
y [View Details ] button: Moves to detail information screen.
Mode
y [COOL] Button: Operates with Cooling Mode.
y [HEAT] Button: Operates with Heating Mode.
Mode Target
Temp ()
Click(Touch) [▲]/[▼] to set the mode set temperature.
y Air-cooled scroll chiller
- COOL: 5 ~15
- HEAT: 35 ~55
y water-cooled scroll chiller
- COOL: 5 ~15
- HEAT: 40 ~57
Demand limit
As measured at 1minute intervals the power consumption of the refrigerator,
the current power consumption does not exceed a target power consumption,
demand rate limit, function to lower the operation rate of the current.
Click(Touch) the [▲] / [▼] button to set a limit on the rate of demand.
y air-cooled scroll chiller: 0~120 (10 units)
y water-cooled scroll chiller: 0, 30~120 (10 units)
[Apply] Button Apply control menu setting to the device.
[Detail. ] Button
Controls details.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG IV AC Smart and is the answer not in the manual?

LG IV AC Smart Specifications

General IconGeneral
BrandLG
ModelIV AC Smart
CategoryAir Conditioner
LanguageEnglish

Related product manuals