40
ENGLISH
USING THE PROGRAM
• Water-cooled scroll chiller Fine Control
You can control the details in the detail control window that appears when you touch the [Detail
control ] button on the control menu of the scroll chiller. Configuration and functions of the
Advanced menu is as follows.
Item Description
Operation
y [ON] Button: Starts the operation of the device.
y [OFF] Button: Stops the operation of the device.
Mode
y [COOL] Button: Operates with Cooling Mode.
y [HEAT] Button: Operates with Heating Mode.
Demand limit
As measured at 1minute intervals the power consumption of the
refrigerator, the current power consumption does not exceed a target
power consumption, demand rate limit, function to lower the operation
rate of the current. Click(Touch) the [▲] / [▼] button to set a limit on the
rate of demand.
y air-cooled scroll chiller: 0~120 (10 units)
y water-cooled scroll chiller: 0, 30~120 (10 units)
Mode Target
Temp
Click(Touch) [▲]/[▼] to setting of the Mode set temperature.
y Air-cooled scroll chiller
- COOL: 5 ~15
- HEAT: 35 ~55
y water-cooled scroll chiller
- COOL: 5 ~15
- HEAT: 40 ~57