Vertiv | Liebert® GXT5™ | Installer/User Guide 111
MODEL GXT5- 5000IRT5UXLN* 5000IRT5UXLE 6000IRT5UXLN* 6000IRT5UXLE
RATING 5000 VA/5000 W 6000 VA/6000 W
ESD IEC/EN EN61000-4-2, Level 4, Criteria B
Radiated Susceptibility IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria B
Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B
Transportation ISTA Procedure 1E
*Only these models are available in the ASIA PACIFIC region.
Table 7-5 UPS Specifications, 8-kVA and 10-kVA models
MODEL GXT5-
80
00IRT5UXLN* 8000IRT5UXLE
10
KIRT5UXLN* 10KIRT5UXLE
RATING 8000 VA/8000 W 10000 VA/10000 W
Dimensions, D×W×H, in. (mm)
Unit 430 × 630 × 217 (16.9 × 24.8 × 8.5)
Shipping 600 × 800 × 520 (23.6 × 31.5 × 20.5)
Weight, kg (lb)
Unit 74.5 (164.2) 74.5 (164.2)
Shipping 95 (209.4) 93 (205) 95 (209.4) 93 (205)
Input AC Parameters
Operating Frequency,
Nom.
50 or 60 Hz (factory-default is 50 Hz)
Factory-default
VAC
230 VAC
Operating voltage
range without battery
operation
176 to 288 VAC (100 to 176VAC with power derating)
Maximum Allowable
VAC
288 VAC
Input frequency
without battery
operation
40 to 70 Hz