Vertiv | Liebert® GXT5™ | Installer/User Guide 113
MODEL GXT5-
8000IRT5UXLN* 8000IRT5UXLE 10KIRT5UXLN* 10KIRT5UXLE
RATING 8000 VA/8000 W 10000 VA/10000 W
Agency
Sa
fety*
IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
EMI/EMC/C-Tick
EMC
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A)
CISPR22 Class A (RFI)
ESD IEC/EN EN61000-4-2, Level 4, Criteria B
Radiated
Susceptibility
IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast
Transient
IEC/EN EN61000-4-4, Level 4, Criteria B
Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B
Transportation
ISTA Procedure 1
E
Table 7-6 UPS Specifications, 16-kVA and 20-kVA models
MODEL GXT5-
1
6K
IRT9UXLN* 16KIRT9UXLE
2
0K
IRT9UXLN* 20KIRT9UXLE
RATING 16000 VA/16000 W 20000 VA/20000 W
Dimensions, D×W×H, in. (mm)
Unit 430 × 630 × 394 (16.9 × 24.8 × 15.5)
Shipping 800 × 1200 × 710 (31.5 × 47.2 × 27.9)
Weight, kg (lb)
Unit 135.2 (298)
Shipping 190 (418.9) 186.7 (411.6) 190 (418.9) 186.7 (411.6)
Input AC Parameters
Operating
Frequency,
Nom.
50 or 60 Hz (factory-default is 50 Hz)
Factory-default
VAC
230 VAC
Operating voltage
range without
battery
operation
176 to 288 VAC (100 to 176 VAC with power derating)
Maximum
Allowable
VAC
288 VAC
Input frequency
without battery
operation
40 to 70 Hz
Input Power
Connection
Input terminal block
*Only these models are available in the ASIA PACIFIC region.