Vertiv | Liebert® GXT5™ | Installer/User Guide 121
Table 7-16 Battery Run Time in Minutes Model: 6-kVA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
% VA W Minutes
10 600 600 100.0 226.0 357.5 489.0 621.0 752.5 884.5 1016.0 1148.0 1279.5 1411.5
20 1200 1200 48.0 107.0 172.0 242.0 312.0 382.0 452.0 522.0 592.0 661.5 731.5
30 1800 1800 29.0 70.0 110.0 154.0 201.5 249.5 297.5 345.5 393.0 441.0 489.0
40 2400 2400 19.5 50.5 81.5 112.5 145.0 181.5 218.0 254.5 291.0 327.5 364.0
50 3000 3000 14.5 38.5 63.5 88.0 113.0 138.5 168.0 197.0 226.5 256.0 285.5
60 3600 3600 11.0 30.0 51.0 72.0 92.5 113.5 134.0 158.5 183.5 208.0 232.5
70 4200 4200 9.0 24.0 42.0 60.5 78.0 96.0 113.5 131.5 152.5 173.5 194.5
80 4800 4800 7.5 20.0 35.5 51.5 67.0 82.5 98.5 114.0 129.5 147.5 166.0
90 5400 5400 6.0 17.0 30.5 44.5 58.5 72.5 86.5 100.5 114.0 128.0 143.5
100 6000 6000 5.5 14.5 26.0 39.0 51.5 64.5 77.0 89.5 102.0 114.5 127.0
Table 7-17 Battery Run Time in Minutes Model: 8-kVA.Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
% VA W Minutes
10 800 800 75.0 166.0 267.5 369.0 471.0 572.5 674.5 776.0 878.0 979.5 1081.0
20 1600 1600 33.5 79.0 124.5 176.0 229.5 283.0 336.5 390.0 443.5 496.5 550.0
30 2400 2400 19.5 50.5 81.5 112.5 145.0 181.5 218.0 254.5 291.0 327.5 364.0
40 3200 3200 13.0 35.0 59.0 82.0 105.5 128.5 155.0 183.0 210.5 238.0 265.5
50 4000 4000 9.5 26.0 45.0 64.0 82.5 101.0 120.0 139.5 161.5 183.5 206.0
60 4800 4800 7.5 20.0 35.5 51.5 67.0 82.5 98.5 114.0 129.5 147.5 166.0
70 5600 5600 6.0 16.0 29.0 42.5 56.0 69.5 83.0 96.5 110.0 123.5 137.5
80 6400 6400 4.5 13.5 24.0 35.5 48.0 59.5 71.5 83.0 95.0 106.5 118.5
90 7200 7200 4.0 11.5 20.5 30.5 41.0 52.0 62.5 73.0 83.5 94.0 104.5
100 8000 8000 3.5 9.5 17.5 26.5 36.0 45.5 55.5 64.5 74.0 83.5 93.0