Table 7-20 Battery Run Time in Minutes Model: 20-kVA.Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
% VA W Minutes
10 2000 2000 62.5 136.0 222.5 309.5 396.5 483.0 570.0 656.5 743.5 830.5 917.0
20 4000 4000 26.0 64.0 101.0 139.5 183.5 228.0 272.5 316.5 361.0 405.0 449.5
30 6000 6000 14.5 39.0 64.5 89.5 114.5 140.5 170.5 200.0 230.0 259.5 289.5
40 8000 8000 9.5 26.5 45.5 64.5 83.5 102.5 121.5 141.5 164.0 186.5 209.0
50 10000 10000 7.0 19.5 34.5 50.0 65.0 80.5 95.5 111.0 126.0 142.5 161.0
60 12000 12000 5.5 15.0 27.0 40.0 53.0 65.5 78.5 91.5 104.0 117.0 129.5
70 14000 14000 4.0 12.0 21.5 32.5 43.5 55.0 66.0 76.5 87.5 98.5 109.5
80 16000 16000 3.5 10.0 18.0 27.0 36.5 46.5 56.5 66.0 75.5 85.0 94.5
90 18000 18000 3.0 8.5 15.0 23.0 31.0 40.0 48.5 57.5 66.0 74.5 83.0
100 20000 20000 2.5 7.0 13.0 19.5 27.0 34.5 42.5 50.5 58.0 66.0 73.5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert Vertiv GXT5 and is the answer not in the manual?

Liebert Vertiv GXT5 Specifications

General IconGeneral
Output Voltage230V
TopologyDouble Conversion Online
Frequency50/60 Hz
Operating Temperature0°C to 40°C
DimensionsVaries by model
WeightVaries by model
Form FactorRack/Tower
Battery TypeValve Regulated Lead Acid (VRLA)
Communication PortsUSB, RS-232
EfficiencyUp to 95%
Typical Recharge Time3 hours to 90%
Storage Temperature-15°C to 40°C
Humidity0% to 95% non-condensing